Hyperchill Laser

Parker Zander Industrial Process Water Chillers for Non-ferrous Laser Equipment

Hyperchill industrial process water chiller for non-ferrous laser equipment from Parker Zander

  Models

Specifications

Drag your finger across the table to scroll

Model ICL 005 ICL 007 ICL 010 ICL 015 ICL 022 ICL 029 ICL 039 ICL 046 ICL 057
Cooling capacity(1) kW 5.6 7.9 10.9 16.6 25.7 31.6 43.9 52.1 68.8
Compr. absorbed power(1) kW 1.4 1.9 2.5 3.9 4.5 5.9 8.1 11.2 13.4
Cooling capacity(2) kW 5.0 7.0 9.4 14.1 22.6 27.8 40.8 48.0 60.3
Compr. absorbed power(2) kW 1.6 2.1 2.7 4.2 5.5 7.1 9.8 13.4 15.9
Power Supply V/1Ph/Hz 230/1/60 460/3/60
Controller digital microprocessor digital PLC
Protection class IP33 IP44 IP54
Refrigerant R407C

Compressors
Type hermetic piston hermetic compliant scroll
Compressors / circuits 1/1
Expansion device capillary thermostatic valve (MOP)

Evaporator
Type brazed plate
Pressure drops(1) psid 0.77 1.29 3.40 7.03 5.97 5.31 5.81 4.86 6.63

Fans
Type axial
Quantity 1 2 3
Max. absorbed power kW 0.12 0.35 0.78 0.61
Total air flow cfm 1355 1120 2415 2060 4000 5415 7298 7063 10242

Pump P30
Type peripheral centrifugal
Max. absorbed power kW 0.37 0.5 1.34 2.28
Water flow(1) (nom/max) GPM 4/11 5/11 7/26 11/26 16/42 21/42 29/79 34/79 43/79
Head pressure(1) (nom/min) psi 43/8 36/8 43/30 41/30 40/25 38/25 40/31 38/31

Pump P50
Type peripheral centrifugal
Max. absorbed power kW 0.75 2.2 3.0
Water flow(1) (nom/max) GPM 4/12 5/12 7/21 11/22 16/40 21/40 29/55 34/55 43/55
Head pressure(1) (nom/min) psi 82/31 74/31 74/50 71/50 82/54 78/54 68/52 66/52 65/52

Tank capacities, connections, and weights
Water connections in 3/4" 1" 1-1/4" 1-1/2"
Tank capacity gal 8 18 37
Weight lbs 200 243 322 344 571 708 783 827 992

Noise level
Sound pressure (3) dB (A) 52 50 53 52 55

(1) at water in/out temperature = 59/68°F (15/20°C), glycol 0%, ambient temperature 77°F (25°C). Net cooling capacity, without pump heat load.
(2) at water in/out temperature = 60/70°F (16/21°C), glycol 0%, ambient temperature 95°F (35°C). Net cooling capacity, without pump heat load.
(3) weights are inclusive of pallet and refrigerant charge.
(4) referred to free field conditions at a distance of 10 m from unit, measured on condenser side.


Correction Factors for the Calculation of the Cooling Capacity(1)

Drag your finger across the table to scroll

A) ambient temperature (air-cooled models)
correction factor (f1)
°F (°C) 41 (5)
1.05
50 (10)
1.05
59 (15)
1.05
68 (20)
1.05
77 (25)
1.00
86 (30)
0.95
95 (35)
0.89
105 (40)
0.83
113 (45)
0.77
B) water outlet temperature
correction factor (f2)
°F (°C) 41 (5)
0.72
50 (10)
0.86
59 (15)
1.00
68 (20)
1.05
77 (25)
1.10
 
C) glycol (in weight)
correction factor (f3)
% 0
1.00
10
0.99
20
0.98
30
0.97
 

(1) at water in/out temperature = 59/68°F (15/20°C), glycol 0%, ambient temperature 77°F (25°C). Net cooling capacity, without pump heat load.

To obtain the required cooling capacity, multiply the value at nominal conditions by the correction factors (i.e. cooling capacity = P x f1 x f2 x f3, where P is the cooling capacity at conditions (1)). Hyperchill Laser, in its standard configuration, can operate up to ambient temperatures of max 113°F (45°C) and min. 41°F (5°C) and water temperatures of max. 86°F (30°C) inlet and min. 32°F (0°C) outlet. The correction factors are approximative; for a precise selection, always refer to the software selection program.


  Features

Features & Benefits

  • "Compliant" scroll compressors.
  • High efficiency evaporator.
  • Integrated stainless steel pump.
  • High-density polyethylene storage tank.
  • Advanced microprocessor.
  • Flexibility of use.
  • High operating limits.
  • Extensive range of accessories.
  • Environmentally friendly refrigerant - R407C.
  • Preventative maintenance agreements available.
  • Worldwide product support.

Description

Hyperchill Laser Chillers offer all the technical features of the Hyperchill Process Water Chiller range: compact and reliable machines designed for industrial applications and manufactured with the highest quality and safety standards.

Hyperchill Laser Chillers are designed to meet the needs of many applications which require stable working conditions with maximum quality and cleanness of the process fluid. Laser marking, cutting and welding are typical industrial processes where the characteristics of the Hyperchill Laser Chillers are necessary to obtain the very best performance and to optimize the production processes.

  Dimensions

Drag your finger across the table to scroll

Model ICL 005 ICL 007 ICL 010 ICL 015 ICL 022 ICL 029 ICL 039 ICL 046 ICL 057
Width ins 21 39 65 87
Height ins 30 22 31
Depth ins 32 58 54

  Catalogs

  Contact mdi

Please fill out the form below and your personal mdi product expert will email you your quote. The more information that you provide the quicker we can send you a quote. Sending an incomplete quote request could mean that we have to contact you for necessary information before sending your quote. And know that our knowledgeable sales staff is standing by to help you with your order and with any questions.

In a rush? Use our Quick Contact form to get in touch with us fast!

If you have about five minutes to spare, though, you can save time on the quoting process by filling out the form below.






Please include your contact information so that we may reply to your request. Your contact information is private and will not be sold to any third party or used negatively in any way.







mdi does not advertise prices online. The cost of products is subject to change over time. In order to extend to you the best price that we can offer, we prefer to create written and emailed quotes which reflect any discounts or promotions currently available. Some products can be quoted over the phone, and expediting quotes and orders is always available per request.

See our Terms and Conditions for more information about the mdi sales process.


Call us any time Monday through Friday 7:30 AM to 5:30 PM ET.

Phone: (727) 835-0649 | Toll Free: 800-761-4298
Fax: (813) 571-0422 | Email or Fill Out the Form Above